The Design of Reinforced Masonry and Precast Concrete Lintels
Matthew
Stuart, P.E., S.E., P.Eng.
Course Outline
The focus of
this one hour online course is the design of reinforced concrete masonry lintels
(commonly referred to as bond beams) and precast reinforced concrete lintels.
Information is also provided on the how loads supported by lintels are evaluated
in light of the arching action of masonry.
This course includes a multiple choice quiz at the end.
Learning Objective
At
the conclusion of this course, the student will:
Course Introduction
Lintels are beams that support masonry above openings in walls. Typically lintels for concrete masonry walls are constructed of either masonry bond beams or precast concrete beams. Masonry bond beams are constructed of unit masonry blocks in the field. These types of lintels require that shoring first be erected to support the bond beam elements during construction until the masonry and grout achieves the necessary strength. Precast concrete lintels are typically fabricated offsite and shipped to the job site for erection. In either case, bond beam and precast lintels have the advantage over steel lintels in that they do not have to be fireproofed for load bearing walls and can typically be installed by the same contractor responsible for the construction of the wall.Course Content
The
focus of this course is the design of reinforced concrete masonry lintels (commonly
referred to as bond beams) and precast reinforced concrete lintels. The information
and examples presented in this course do not include provisions for shear reinforcement.
This is because it is not common practice to use shear reinforcement, or stirrups,
in masonry lintels, particularly bond beam lintels.
The
methods of analysis presented are allowable stress design and strength design
in which service loads are increased by load factors. Allowable stress design
(ASD) criterion is based on the 1995 Building Code Requirements for Masonry
Structures (ACI 530). Strength design criteria will be provided separately for
reinforced concrete (precast) masonry lintels. The design of precast concrete
lintels is based on the 1995 Building Code Requirements for Structural Concrete
(ACI 318).
Materials
used in the construction of masonry lintels include bond beam sections, mortar,
grout and steel. Examples of different types of lintels are shown below:

Vertical
loads carried by lintels typically include; (1) distributed loads from the dead
weight of the lintel and the masonry wall above the lintel, any floor and or
roof dead and live loads supported by the masonry and (2) concentrated loads
from floor beams, roof joists and other members which frame directly into the
wall. Depending on the construction of the wall and nature of the framing that
is supported, distributed loads acting on a lintel can be further separated
into four load types:
In
some instances, the masonry wall will distribute loads so that they do not act
on the lintel. This is called arching action of masonry and is based on the
amount of masonry that is above the opening over which the lintel spans. The
impact of distributed and concentrated loads on lintels is affected by arching
action. Arching action can be assumed if the following criteria are met; (1)
the masonry is laid in running not stacked bond, (2) sufficient wall height
above the lintel exists to form a 45 degree triangle with at least 8 inches
of wall height occulting above the top of the arch and (3) minimum end bearing
is maintained. For this last criterion it is important to recognize that arching
action results horizontal thrust forces at the base of the arch. This thrust
must be accounted for in order for arching action to occur. Therefore it is
not recommended that arching action be assumed above openings that occur next
to corners of a building or at locations where the adjacent block at the bottom
of the arch is discontinuous.
As
already indicated, the design loads applied to a lintel depend on whether arching
action is present or not. In the case of the weight of wall supported by a lintel,
arching will cause only the weight of wall within the triangular area below
the top or apex of the arch to impact the lintel. The triangular load has a
base equal to the effective span length of the lintel and a height as shown
below:

Where,
L = 4 x Wall Thickness +
Width of Beam
w = P / L
The load is then resolved onto the lintel as a uniform load with a maximum length equal to four times the wall thickness plus the width of bearing. The magnitude of the load per unit length is computed by dividing the concentrated load by this same length: w=P/L. An example of the impact of a concentrated load offset from a lintel opening is shown below:
In some cases a series of
concentrated loads may be considered as uniform on a lintel. The criteria as
to whether a series of concentrated loads can be assumed as an equivalent uniform
load on the lintel is a function of the spacing of the loads. If this criterion
is met the equivalent uniform loading can be neglected if the bearing elevation
of the beams occurs above any arching action that is present. Otherwise, each
concentrated load must be resolved into an equivalent uniform load independently.
As indicated above, in some cases a series of concentrated roof or floor loads on a wall laid in running bond may be considered as an equivalent uniform load. This condition applies to relatively light loads spaced closely together such as floor joists or roof rafters in residential or other similar construction. Concentrated loads of these types may be considered as uniform as shown below:

In general these types of concentrated loads can be considered as uniformly distributed if the total height of masonry between the top of the lintel and the bearing elevation of the joists is at least 1/3 the center-to-center spacing of the loads.
Heavier
concentrated loads, such as that which may be encountered in industrial and
commercial buildings can also be considered to act as equivalent distributed
loads as shown below:
Where, SL
is less or equal to 4'-0" 
In general, uniform loading can be assumed whenever the spacing of the loads is less than 4 feet and the wall height above the lintel is greater than 1/2 the load spacing. Therefore heavy loads spaced more than 4 feet apart in general should be considered as individual concentrated loads and distributed to the lintel as equivalent uniform load independently.
Concentrated loads over stack bond masonry are not transferred or distributed across vertical joints. An example of this condition is shown below. Loads should not be assumed to be transmitted across vertical joints even if joint reinforcement is used in the wall construction.

It is also common for an engineer to be faced with the prospect of designing and detailing a lintel for a new opening to be cut in an existing wall. Examples of steel lintels that can be installed before the demolition of a new opening occurs are shown below:
Small Masonry Opening in Existing Wall

Large Masonry Opening in Existing Wall

In some cases, however, it is necessary to use either a masonry or precast lintel for a new opening in an existing wall. For this situation it is necessary to take advantage of the arching action of the masonry wall above the opening. The arching action allows for the complete removal of the masonry, as shown below, in order to erect the lintel. The masonry above the lintel is simply in-filled above the lintel after the new opening is complete.
New Masonry or Concrete Lintel in Existing Wall

The following ASD methods and parameters apply to unit masonry lintels. The ASD method compares the design stress produced in a member by applied loads to allowable stresses permitted by the Code. In ASD, the masonry is assumed to resist the compressive forces. The tensile strength of masonry units, mortar and grout is neglected. All tensile stresses therefore are assumed to be resisted by the reinforcing steel. The equations governing ASD are listed below:

Strength design is a method of analysis that compares factored loads to the design strength of the member. Precast concrete lintels are typically designed using this method. This method allows for the load, which produces failure, to be predicted. This method also allows for the failure mode to be controlled so that ductile rather than compressive failure occurs first. Strength design flexural compression, tension and shear are determined in accordance with principles established by the Code. The tensile strength of masonry is neglected and the resulting nominal strengths are computed using the governing equations listed below:
The
allowable flexural stress for masonry lintels, Fb, is equal to 1/3 of f’m. The
allowable shear stress for masonry lintels is equal to the square root of f’m.
For steel, in ASD, the allowable stress is 24,000 psi for grade 60 reinforcing
bars. To summarize:
Reinforced
concrete masonry strength design reduction factors for flexure and shear are
based on ACI 530 and are 0.8 and 0.6, respectively. Precast concrete strength
reduction factors are based on ACI 318 and are 0.9 for flexure and 0.85 for
shear.
The
effective span length of a lintel is defined as the clear span plus the depth
of the member but not greater than the distance measured between the support
centers. ACI 530 states that end bearing should not be less than 4 inches. As
an integral part of a wall, lintels are typically considered as laterally supported.
Lintel deflection is limited to the effective span divided by 600 or .3” when
used to support unreinforced masonry per ACI 530. The commentary of this same
Code waives the L/600 criterion if the supported wall is considered reinforced
masonry.
The
effective compressive width, b, of a lintel should be taken as the nominal width
less 3/8”. For example, you should use 7-5/8” as the actual width of an 8” CMU
block. The effective depth, d, is also taken as the nominal depth less 3/8”.
The depth of cover and half the diameter of the reinforcing bar should also
be subtracted from this depth. Limitations on reinforcing bars as placed in
masonry bond beams is shown in the detail below:
Course Summary
The
design of masonry and concrete lintels requires an understanding of the load
path mechanisms of unit masonry walls. The natural arching action of running
bond masonry walls often provides an alternate load path for both uniform and
concentrated loads located above a lintel. Concrete masonry lintels are most
often designed using the allowable stress design or service stress method of
analysis. The design precast concrete lintels must comply with the ultimate
strength design provision of ACI 318.
Please
use the information you read in this course to answer the quiz questions.
Related Links
For additional technical information related to this subject, please visit the following websites or web pages: